Sign In | Join Free | My disqueenfrance.com |
|
Brand Name : Fanke
Model Number : CHX(LYY) Series
Certification : ISO9001
Place of Origin : CHINA
MOQ : One Set
Price : Negotiable
Payment Terms : L/C, T/T
Supply Ability : 2sets / 2months
Delivery Time : 45~60 working days
Packaging Details : Export standard wooden case with fumigation free
Test Principle : Variable Inductance Resonant Circuit
Usage : On-site AC Withstand Voltage Test For HV GIS or CVT
Design Feature : Fast installation and fast recycling , PD free
Component : Test reactor , control console , voltage regulator cabinet , standard voltage divider
Test Frequency : 50Hz/60Hz
Duty Cycle : 15mints
Test Accuracy : No Less Than 1.5%
Output Waveform : Good Sine Wave
Special For : On-site Test For HV or EHV GIS,CVT
Reactor Using Way : One body and Hydraulic Type for standing and recycling
Test Standard : IEC60060-1:2010;IEC 62271-203:2011 for GIS
Variable Inductance Resonant Withstand Voltage Test Set , Hydraulic Type HV Test Set With Resonance , CVT Testing
I. Application :
CHX-(LYY) Hydraulic Automatic Elevating Series Resonance Test Devices mainly applies to AC voltage withstand and partial discharge detecting of high voltage electrical apparatus no more than 800KV. Especially suitable for field calibration test for different level of CVT and AC voltage withstand test for different level of HV.GIS and GIL.
Fanke successfully developed AC voltage withstand and PD detection device through combination of series resonance circuit theory and altering traditional test reactor structure from technical feature of materialogy,electromagnetic property,auto machinery and hydraulic transmission,which makes field testing much more suitable and efficient
II. Scope of Application
Used for power frequency PD-free high voltage power source for field calibration test of CVT angular difference and ratio error.
Used for AC voltage withstand test and PD test of HV.GIS, HV.GIL,HV.switch, mutual inductor, and bushing with voltage no more than 800KV
III. Main Components:
IV. Fast standing and recycling Figure
1.Multit tapped design for both reactors able to meet power frequency high voltage output needed by field calibration for CVT below 50Hz.
2.Matching up with variable-frequency power source to complete AC voltage withstand test for electrical equipment such as GIS, breaker,
mutual inductor, insulator ranges of 110KV---500KV.
VI. General Technical Data:
Rated capacitor: 400KVA ~ 1000KVA
Rated voltage : 400KV ~ 800KV
Rated current : 1A ~ 2A
Working power : supply single phase 380V,50Hz/60Hz
System quality factor value : Q ≥ 50
Duty cycle and temperature rise : after 15mints of rated operation, the winding temperature rise ≤ 65K
Noise: ≤ 65dB
Altitude: ≤ 3000m
Environment temperature: -25℃ ~45℃,Relative humidity ≤ 90% ,no condensation
Size: see the above figure
VI.Accessories
VII. Other Typical Model
Model | Rated voltage | Rated output current | Rated output capacity | Application (From 45Hz starting) |
CHX-(LYY) -400KVA/400KV | 200KV*2 | 2A@200KV | 400KVA | For 132KV and below class GIS |
1A@400KV | For 132KV and below class CVT | |||
CHX-(LYY) -800KVA/400KV | 200KV*4 | 4A@200KV | 800KVA | For 132KV and below class GIS |
2A@400KV | For 132KV and below class CVT | |||
CHX-(LYY) -800KVA/400KV,800KV | 400KV*2 | 2A@400KV | 800KVA | For 400KV and below class GIS |
1A@800KV | For 400KV and below class CVT | |||
CHX-(LYY) -1600KVA/400KV,800KV | 400KV*4 | 4A@400KV | 1600KVA | For 400KV and below class GIS |
2A@800KV | For 400KV and below class CVT | |||
Special requirement can be made by order |
![]() |
Variable Inductance AC Resonant Test System Hydraulic Type For HV GIS Or CVT Images |